SPECIFICATIONS: MSZ-FX24NL & MUZ-FX24NLHZ |
|
|
Cooling at 95F^{1} |
Maximum Capacity |
Btu/h |
26,500 |
|
Rated Capacity |
Btu/h |
20,800 |
|
Minimum Capacity |
Btu/h |
2,500 |
|
Maximum Power Input |
W |
3,370 |
|
Rated Power Input |
W |
1,560 |
|
Moisture Removal |
Pints/h |
4 |
|
Sensible Heat Factor |
- |
0.78 |
|
Power Factor [208V / 230V] |
% |
98 / 98 |
Heating at 47F^{2} |
Maximum Capacity |
Btu/h |
36,200 |
|
Rated Capacity |
Btu/h |
19,800 |
|
Minimum Capacity |
Btu/h |
5,500 |
|
Maximum Power Input |
W |
3,590 |
|
Rated Power Input |
W |
1,500 |
|
Power Factor [208V / 230V] |
% |
100 / 100 |
Heating at 17F^{3} |
Maximum Capacity |
Btu/h |
29,200 |
|
Rated Capacity |
Btu/h |
13,600 |
|
Maximum Power Input |
W |
3,800 |
|
Rated Power Input |
W |
1,320 |
Heating at 5F^{4} |
Maximum Capacity |
Btu/h |
26,600 |
|
Maximum Power Input |
W |
3,790 |
Heating at -5F^{6} |
Maximum Capacity |
Btu/h |
22,400 |
Heating at -10F^{7} |
Maximum Capacity |
Btu/h |
19,800 |
Heating at -22F^{9} |
Maximum Capacity |
Btu/h |
11,700 |
Efficiency |
SEER2 |
|
23.5 |
|
EER2^{1} |
|
13.35 |
|
HSPF2 [IV] |
|
10.5 |
|
COP at 47°F^{2} |
|
3.86 |
|
COP at 17°F at Maximum Capacity^{3} |
|
2.24 |
|
COP at 5°F at Maximum Capacity^{4} |
|
2.04 |
|
COP at -5°F at Maximum Capacity^{6} |
|
1.84 |
|
COP at -10°F at Maximum Capacity^{7} |
|
1.72 |
|
ENERGY STAR^{®} Certified |
|
Yes |
Electrical |
Voltage, Phase, Frequency |
V AC / V AC, , Hz |
208 / 230, 1, 60 |
|
Guaranteed Voltage Range |
V AC |
187 - 253 |
|
Voltage: Indoor - Outdoor, S1-S2 |
V AC |
208/230 |
|
Voltage: Indoor - Outdoor, S2-S3 |
V DC |
24 |
|
Short-circuit Current Rating [SCCR] |
kA |
5 |
|
Recommended Fuse/Breaker Size (Outdoor) |
A |
20 |
|
Recommended Wire Size [Indoor - Outdoor] |
AWG |
14 |
Indoor Unit |
MCA |
A |
1 |
|
Fan Motor Output |
W |
40 |
|
Airflow Rate at Cooling, Dry |
CFM |
272, 378, 484, 586, 720 |
|
Airflow Rate at Cooling, Wet |
CFM |
231, 321, 411, 498, 612 |
|
Airflow Rate at Heating, Dry |
CFM |
272, 353, 470, 586, 749 |
|
Sound Pressure Level [Cooling] |
dB (A) |
27, 34, 41, 47, 53 |
|
Sound Pressure Level [Heating] |
dB (A) |
26, 32, 40, 47, 55 |
|
Dual Barrier Coating on Heat Exchanger |
|
Yes |
|
External Finish Color |
|
Munsell 1.0Y 9.2/0.2 |
|
Unit Dimensions (W x D x H) |
inch x inch x inch
[mm x mm x mm] |
39 -9/32 x 9-3/4 x 12 [998 x 247 x 305] |
|
Package Dimensions (W x D x H) |
inch x inch x inch
[mm x mm x mm] |
43 -5/16 x 12-3/4 x 15-3/4 [1,100 x 330 x 400] |
|
Unit Weight |
lbs [kg] |
31.60 [14.30] |
|
Package Weight |
lbs [kg] |
36.70 [16.60] |
|
Fan Motor Type |
|
DC Motor |
IDU Operating Temp. Range |
Cooling Intake Air Temp [Maximum / Minimum] |
°FDB, °FWB / °FDB,
°FWB |
90, 73 / 67, 57 |
|
Heating Intake Air Temp [Maximum / Minimum] |
°FDB |
80 / 70 |
|
NOTES
^{1} Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB)
^{2} Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB)
^{3} Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB)
^{4} Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB)
^{6} Heating at -5°F (Indoor: 70°F DB, 60°F WB // Outdoor: -5°F DB, -6°F WB)
^{7} Heating at -10°F (Indoor: 70°F DB, 60°F WB // Outdoor: -10°F DB, -11°F WB)
^{9} Heating at -22°F (Indoor: 70°F DB, 60°F WB // Outdoor: -22°F DB, -23°F WB)
^{*} Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures. |
|
Specifications are subject to change without notice. |