Cooling at 95F1 |
Maximum Capacity |
Btu/h |
13,400 |
Rated Capacity |
Btu/h |
12,000 |
Minimum Capacity |
Btu/h |
3,600 |
Maximum Power Input |
W |
1,430 |
Rated Power Input |
W |
960 |
Moisture Removal |
Pints/h |
2 |
Sensible Heat Factor |
- |
0.82 |
Power Factor [208V / 230V] |
% |
98 / 98 |
Heating at 47F2 |
Maximum Capacity |
Btu/h |
15,500 |
Rated Capacity |
Btu/h |
12,200 |
Minimum Capacity |
Btu/h |
4,500 |
Maximum Power Input |
W |
2,140 |
Rated Power Input |
W |
990 |
Power Factor [208V / 230V] |
% |
100 / 100 |
Heating at 17F3 |
Maximum Capacity |
Btu/h |
9,000 |
Rated Capacity |
Btu/h |
7,800 |
Maximum Power Input |
W |
1,670 |
Rated Power Input |
W |
900 |
Heating at 5F4 |
Maximum Capacity |
Btu/h |
8,600 |
Maximum Power Input |
W |
1,400 |
Heating at -5F6 |
Maximum Capacity |
Btu/h |
8,300 |
Efficiency |
SEER2 |
|
20 |
EER21 |
|
12.5 |
HSPF2 [IV] |
|
10 |
COP at 47°F2 |
|
3.61 |
COP at 17°F at Maximum Capacity3 |
|
1.56 |
COP at 5°F at Maximum Capacity4 |
|
1.8 |
COP at -5°F at Maximum Capacity6 |
|
1.76 |
ENERGY STAR® Certified |
|
Yes |
Electrical |
Voltage, Phase, Frequency |
V AC / V AC, ø, Hz |
115 / 115, 1, 60 |
Guaranteed Voltage Range |
V AC |
103 - 127 |
Voltage: Indoor - Outdoor, S1-S2 |
V AC |
115 |
Voltage: Indoor - Outdoor, S2-S3 |
V DC |
24 |
Short-circuit Current Rating [SCCR] |
kA |
5 |
Recommended Fuse/Breaker Size (Outdoor) |
A |
20 |
Recommended Wire Size [Indoor - Outdoor] |
AWG |
14 |
Indoor Unit |
MCA |
A |
1.4 |
Fan Motor Output |
W |
30 |
Airflow Rate at Cooling, Dry |
CFM |
168, 243, 333, 468 |
Airflow Rate at Cooling, Wet |
CFM |
151, 219, 300, 422 |
Airflow Rate at Heating, Dry |
CFM |
173, 239, 343, 395 |
Sound Pressure Level [Cooling] |
dB (A) |
22, 30, 38, 47 |
Sound Pressure Level [Heating] |
dB (A) |
23, 30, 38, 43 |
Drain Pipe Size O.D. |
inch [mm] |
5/8 [15.88] |
External Finish Color |
|
Munsell 0.7PB 9.2/0.4 |
Unit Dimensions (W x D x H) |
inch x inch x inch [mm x mm x mm] |
33 x 9-1/4 x 11-1/32 [838 x 235 x 280] |
Package Dimensions (W x D x H) |
inch x inch x inch [mm x mm x mm] |
36 x 13-1/4 x 11-1/2 [920 x 340 x 300] |
Unit Weight |
lbs [kg] |
20 [9] |
Package Weight |
lbs [kg] |
24 [10.50] |
Fan Motor Type |
|
DC Motor |
IDU Operating Temp. Range |
Cooling Intake Air Temp [Maximum / Minimum] |
°FDB, °FWB / °FDB,
°FWB |
90, 73 / 67, 57 |
Heating Intake Air Temp [Maximum / Minimum] |
°FDB |
80 / 70 |
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 6Heating at -5°F (Indoor: 70°F DB, 60°F WB // Outdoor: -5°F DB, -6°F WB)
* Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures. |
Outdoor Unit |
MCA |
A |
17 |
MOCP |
A |
29 |
Fan Motor Full Load Amperage |
A |
0.5 |
Fan Motor Output |
W |
55 |
Airflow Rate Cooling |
CFM |
1,344 |
Airflow Rate Heating |
CFM |
1,152 |
Defrost Method |
|
Reverse Cycle |
Coating on Heat Exchanger (Bluefin, Sea Coast) |
|
Yes, Yes |
Sound Pressure Level, Cooling1 |
dB (A) |
49 |
Sound Pressure Level, Heating2 |
dB (A) |
51 |
Compressor Type |
|
Twin Rotary |
Compressor Model |
|
SRB140FQHMC |
Compressor Oil [Type // Charge] |
Type // oz |
RM68EH // 11.8 |
External Finish Color |
|
Munsell 3Y 7.8/1.1 |
Base Pan Heater |
|
Optional |
Unit Dimensions (W x D x H) |
inch x inch x inch [mm x mm x mm] |
31/-1/2 x 11-1/4 x 21/5/8 [800 x 285 x 550] |
Package Dimensions (W x D x H) |
inch x inch x inch [mm x mm x mm] |
36 x 13-1/4 x 11-1/2 [920 x 340 x 300] |
Unit Weight |
lbs [kg] |
20 [9] |
Package Weight |
lbs [kg] |
24 [10.50] |
ODU Operating Temp. Range |
Cooling Intake Air Temp [Maximum / Minimum*] |
°FDB |
115 / 14 |
Cooling Thermal Lock-out / Re-start Temperatures** |
°FDB |
-1 / 3 |
Heating Intake Air Temp [Maximum / Minimum] |
°FDB, °FWB / °FDB,
°FWB |
75, 65 / -5, -6 |
Heating Thermal Lock-out / Re-start Temperatures** |
°FDB |
-14 / -4 |
Refrigerant |
Type |
|
R454B |
Pre-Charged Refrigerant Amount |
lbs, oz |
2, 2 |
Maximum Pre-Charged Piping Length |
ft [m] |
25 [7.50] |
Additional Refrigerant Charge Per Additional Piping Length |
oz/ft |
0.22 |
Piping |
Gas Pipe Size O.D. [Flared] |
inch [mm] |
3/8 [9.52] |
Liquid Pipe Size O.D. [Flared] |
inch [mm] |
1/4 [6.35] |
Maximum Piping Length |
ft [m] |
65 [20] |
Maximum Height Difference |
ft [m] |
40 [12] |
Maximum Number of Bends |
|
10 |
NOTES
1Cooling at 95°F (Indoor: 80°F DB, 67°F WB // Outdoor: 95°F DB, 75°F WB) 2Heating at 47°F (Indoor: 70°F DB, 60°F WB // Outdoor: 47°F DB, 43°F WB) 3Heating at 17°F (Indoor: 70°F DB, 60°F WB // Outdoor: 17°F DB, 15°F WB) 4Heating at 5°F (Indoor: 70°F DB, 60°F WB // Outdoor: 5°F DB, 4°F WB) 6Heating at -5°F (Indoor: 70°F DB, 60°F WB // Outdoor: -5°F DB, -6°F WB)
* Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
** Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode and automatically restarts at these temperatures. |