YMGI Specifications: DC Inverter Mini Split Heat Pump-Multiple Zone-(59)4 Outdoor Units 21SEER |
Model |
Units |
WMMS-48CH-V2B(59)4 |
Cooling Capacity Rating-Standard Comp. Speed |
Btu/h |
34000 |
Min./Max. Cooling Capacity |
Btu/h |
8871 / 35826 |
Heating Capacity Rating-Standard Comp. Speed |
Btu/h |
42500 |
Min./Max. Heating Capacity |
Btu/h |
8871 / 44356 |
Max. Allowed IDU Qty./Capacity Total |
# / Btu/h |
5 / 48,000 |
EER W/W, (Btu/h)/W |
W/W |
3.66 / 12.5 |
COP W/W, (Btu/h)/W |
W/W |
3.70 / 12.62 |
SEER / HSPF |
- |
21.00 / 10.50 |
Air Flow Volume |
CFM |
4531 |
Sound Pressure / Power Level |
dB(A) |
61 / 71 |
Power Supply |
V/Ph/Hz |
208-230/1/60 |
Power Cable Conductor Minimum Size |
AWG |
AWG10, Following NEC |
Recommended HVAC Type Circuit Breaker Size |
Amp. |
40 |
Power Input Cooling / Heating / Rated |
KW |
2.72 / 3.37 / 3.80 |
Current Input Cooling / Heating / Rated |
A |
11.84 / 14.64 / 16.86 |
Compressor Type, Model |
- |
Inverter Rotarty, LD QXAS- D32zX090A |
Compressor Capacity / Input |
W |
12300 / 4150 |
Compressor RLA / LRA |
A |
15.6 / - |
Compressor Thermal Protector KINGERSONS |
- |
Exterior 1NT11L—6233 |
Compressor Crankcase Heater |
W |
40 |
Compressor Oil Type, Charge |
-, OZs |
FV50S, 35.2 |
De-Ice/Snow Heater Power Input |
W |
96 |
De-Ice/Snow Heater Current |
A |
0.4 |
Fan Type / Qty. / Diameter-Height |
- |
Axial-flow / 1 /D570-H152mm |
Motor Model / Type |
- |
SWZ150B, DC |
Motor Insulation Class, Safe Class |
- |
E, IPX4 |
Fan Motor Drive Type, Speed |
- |
Director Drive, 880 |
Fan Motor Power Output / Input |
W |
170 / 240 |
Motor Full Load Amp (FLA) |
A |
0.82 |
Condenser Materials |
- |
Aluminum Fin-Copper Tube |
Permissible Operating Pressure for the Discharge/Suction Sides |
PSI |
600 / 360 |
High/Low Pressure Overload Protector |
PSI |
580 / - |
Cooling Operation Ambient Temperature Range |
F |
0 ~ 118 |
Heating Operation Ambient Temperature Range |
F |
-4 ~ 75 |
Defrosting Method of Heat Pump in
Low Temperature Ambient |
-- |
Automatic Reversing, Fan
Cycling |
Pressure Maitenance Method in Low
Temperature Cooling |
-- |
Automatic Fan Speed Control,
Cycling |
Overload Protector |
- |
Current+Temperature |
Designed for Climate Type, Moisture Protection |
- |
T1, IPX4 |
Refrigerant, Charge |
LBs |
R410A, 8.0 |
Metering Device KINGERSONS |
- |
Electronic expansion valve |
Flare/Nut Valve Size-Liquid |
Inch |
1/4, 1/4, 1/4, 1/4, 1/4 |
Flare/Nut Valve Size-Gas |
Inch |
3/8, 3/8, 3/8, 3/8, 3/8 |
Min. Allowed Copper Line Length/Unit |
Ft. |
15 |
Max. Allowed Copper Line Length-
outdoor to last indoor unit |
Ft. |
80 |
Max. Elevation Difference Allowed-
outdoor unit is below all indoor units |
Ft. |
50, Oil Trap is Not Needed |
Max. Elevation Difference Allowed-
outdoor unit is above indoor units |
Ft. |
50, Oil Trap is Suggested
Every 25' |
Max. Copper Line Length (all together) |
Ft. |
246 |
No Additional Refrigerant Needs to be Added, If Copper Line Length Total is Less Than |
Ft. |
150 |
Refrigerant Charge Rate, If Needed, by
Weight/Ft. of Extra Liquid Line Length |
Ozs/Ft. |
2.32 |
Dimension of Unit Outline (W×D×H) |
Inch |
42.8x17.3x43.4 |
Dimension of Package (W×D×H) |
Inch |
45.6x19.4x48.6 |
Weight-Net / Gross |
LBs |
198 / 216 |
Loading Quantity (20’/40GP/40HQ) |
Units |
22 / 48 / 86 |